EasyManua.ls Logo

ABB RELION 670 SERIES REG670 - Page 217

ABB RELION 670 SERIES REG670
830 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The zero sequence mutual coupling can reduce the reach of distance protection on the
protected circuit when the parallel line is in normal operation. The reduction of the
reach is most pronounced with no current infeed in the IED closest to the fault. This
reach reduction is normally less than 15%. But when the reach is reduced at one line
end, it is proportionally increased at the opposite line end. So this 15% reach reduction
does not significantly affect the operation of a permissive underreaching scheme.
Parallel line out of service and
grounded
GUID-574F8EE5-EAEC-40B8-A615-FDAD2808CD6D v1GUID-8EB3A8EF-119D-4530-8F01-0879A7478E1F v1
Z0m
A B
21
21
en05000222_ansi.vsd
CLOSED
CLOSED
OPEN OPEN
ANSI05000222 V1 EN-US
Figure 86: The parallel line is out of service and grounded
When the parallel line is out of service and grounded at both line ends on the bus bar
side of the line CTs so that zero sequence current can flow on the parallel line, the
equivalent zero sequence circuit of the parallel lines will be according to figure
87.
A
B
C
IEC09000252_1_en.vsd
I
0
I
0
Z
0m
Z
0
-
Z
0m
Z
0
-
Z
0m
IEC09000252 V1 EN-US
Figure 87: Equivalent zero sequence impedance circuit for the double-circuit line
that operates with one circuit disconnected and grounded at both ends
Here the equivalent zero-sequence impedance is equal to Z
0
-Z
0
m in parallel with (Z
0
-
Z
0m
)/Z
0
-Z
0m
+Z
0m
which is equal to equation
45.
2 2
0
0
om
E
Z Z
Z
Z
-
=
EQUATION2002 V4 EN-US (Equation 45)
1MRK 502 071-UUS A Section 8
Impedance protection
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062 211
Application manual

Table of Contents

Related product manuals