EasyManua.ls Logo

ABB RELION 670 SERIES REG670 - Page 309

ABB RELION 670 SERIES REG670
830 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
+
E
-
I, (P, Q)
j X
d
j X
net
+
V
-
+
E
net
-
en06000321.vsd
IEC06000321 V1 EN-US
Figure 145: A generator connected to a power system, represented by an
equivalent single phase circuit
where:
E represents the internal voltage in the generator,
X
d
is the stationary reactance of the generator,
X
net
is an equivalent reactance representing the external power system and
E
net
is an infinite voltage source representing the lumped sum of the generators in the system.
The active power out from the generator can be formulated according to equation
161:
sin
net
d net
E E
P
X X
d
×
= ×
+
EQUATION1540 V1 EN-US (Equation 161)
where:
The angle δ is the phase angle difference between the voltages E and E
net
.
If the excitation of the generator is decreased (loss of field), the voltage E becomes
low. In order to maintain the active power output the angle δ must be increased. It is
obvious that the maximum power is achieved at 90°. If the active power cannot be
reached at 90º static stability cannot be maintained.
The complex apparent power from the generator, at different angles δ is shown in
figure 146. The line corresponding to 90° is the steady state stability limit. It must be
noticed that the power limitations shown below is highly dependent on the network
impedance.
1MRK 502 071-UUS A Section 8
Impedance protection
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062 303
Application manual

Table of Contents

Related product manuals