EasyManua.ls Logo

ABB RELION 670 SERIES REG670 - Page 367

ABB RELION 670 SERIES REG670
830 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The function shall not operate for any of the calculated currents to the protection. The
minimum theoretical current setting (Imin) will be:
Im ,
f
AfB
in MAX I I
EQUATION284 V2 EN-US (Equation 180)
A safety margin of 5% for the maximum static inaccuracy and a safety margin of 5%
for maximum possible transient overreach have to be introduced. An additional 20% is
suggested due to inaccuracy of instrument transformers under transient conditions and
inaccuracy in the system data.
The minimum primary current setting (Is) is:
I
s
= 1.3 × I
min
EQUATION285 V3 EN-US (Equation 181)
In case of parallel lines with zero sequence mutual coupling a fault on the parallel line,
as shown in Figure 179, should be calculated.
~ ~
Z
A
Z
B
Z
L1
A B
I
M
Fault
IED
Z
L2
M
C
Line 1
Line 2
ANSI09000025_2_en.vsd
ANSI09000025 V2 EN-US
Figure 179: Two parallel lines. Influence from parallel line to the through fault
current: I
M
The minimum theoretical current setting (Imin) will in this case be:
I m in M A X I
fA
I
fB
I
M
, ,( )³
EQUATION287 V1 EN-US (Equation 182)
Where:
I
fA
and I
fB
have been described for the single line case.
1MRK 502 071-UUS A Section 9
Current protection
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062 361
Application manual

Table of Contents

Related product manuals