Operate
Angle1(2 ) = 180
o
Power1(2)
P
Q
IEC06000557-2-en.vsd
IEC06000557 V2 EN-US
Figure 200: For reverse power the set angle should be 180° in the overpower
function
TripDelay1(2) is set in seconds to give the time delay for trip of the stage after pick up.
Hysteresis1(2) is given in p.u. of generator rated power according to equation
229.
EQUATION2047 V1 EN-US (Equation 229)
The drop out power will be Power1(2) - Hysteresis1(2).
The possibility to have low pass filtering of the measured power can be made as shown
in the formula:
Section 9 1MRK 502 071-UUS A
Current protection
416 Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Application manual