EasyManua.ls Logo

ABB RELION 670 SERIES REG670 - Page 621

ABB RELION 670 SERIES REG670
830 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
the calculation of circulating currents. The capacitive current is part of the imaginary
load current and therefore essential in the calculation. The calculated circulating
current and the real circulating currents will in this case not be the same, and they will
not reach a minimum at the same time. This might result in a situation when
minimizing of the calculated circulating current will not regulate the tap changers to
the same tap positions even if the power transformers are equal.
However if the capacitive current is also considered in the calculation of the circulating
current, then the influence can be compensated for.
Load
T1
I
L
T2
I
cc....T2
I
cc....T1
V
B
V
L
I
T1
I
T2
I
C
I
T
2
-I
C
Load
T1
I
L
T2
I
cc....T2
I
cc....T1
V
B
V
L
I
T1
I
T2
I
T2
I
T1
I
T1
I
C
en06000512_ansi.vsd
ANSI06000512 V1 EN-US
Figure 289: Capacitor bank on the LV-side
From figure
289 it is obvious that the two different connections of the capacitor banks
are completely the same regarding the currents in the primary network. However the
CT measured currents for the transformers would be dif
ferent. The capacitor bank
current may flow entirely to the load on the LV side, or it may be divided between the
LV and the HV side. In the latter case, the part of I
C
that goes to the HV side will
divide between the two transformers and it will be measured with opposite direction
1MRK 502 071-UUS A Section 15
Control
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062 615
Application manual

Table of Contents

Related product manuals