230kV Busbar
300/5
4000/5
100 MVA
G
P Q
100 MVA
15.65kV
ANSI09000041-1-en.vsd
15/0.12kV
V
AB ,
V
BC
,
IED
ANSI09000041 V1 EN-US
Figure 311: Single line diagram for generator application
In order to measure the active and reactive power as indicated in figure
311, it is
necessary to do the following:
1. Set correctly all CT and VT data and phase angle reference channel
PhaseAngleRef using PCM600 for analog input channels
2.
Connect, in PCM600, measurement function to the generator CT & VT inputs
3. Set the setting parameters for relevant Measurement function as shown in the
following table:
1MRK 502 071-UUS A Section 17
Monitoring
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062 689