Protected Object
CT 800/1
Wye Connected
IED
ANSI11000026-5-en-.vsd
4
1
2
3
A
IA
IB
IC
B C
IA
IB
IC
SMAI_20_2
BLOCK
REVROT
^GRP2_A
^GRP2_B
^GRP2_C
^GRP2N
AI3P
AI1
AI2
AI3
AI4
AIN
5
ANSI11000026 V5 EN-US
Figure 19: Wye connected three-phase CT set with its wye point away from the protected object
In the example, everything is done in a similar way as in the above described example
(Figure
18). The only difference is the setting of the parameter CTStarPoint of the used
current inputs on the TRM (item 2 in Figure 19 and 18):
CTprim=600A
CTsec
=5A
CTWyePoint=FromObject
The ratio of the first two parameters is only used inside the IED. The third parameter as
set in this example will negate the measured currents in order to ensure that the
currents are measured towards the protected object within the IED.
A third alternative is to have the residual/neutral current from the three-phase CT set
connected to the IED as shown in Figure
19.
1MRK 502 071-UUS A Section 4
Analog inputs
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062 77