EasyManua.ls Logo

ABB relion REF615 - 3.5.3 Functional diagrams

ABB relion REF615
404 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Channel ID text Level trigger mode
22 INRPHAR1 - blk2h Level trigger off
23 T1PTTR1 - operate Level trigger off
24 ARCSARC1 - ARC flt det Level trigger off
ARCSARC2 - ARC flt det
ARCSARC3 - ARC flt det
25 ARCSARC1 - operate Positive or Rising
26 ARCSARC2 - operate Positive or Rising
27 ARCSARC3 - operate Positive or Rising
28 DARREC1 - inpro Level trigger off
29 DARREC1 - close CB Level trigger off
30 DARREC1 - unsuc recl Level trigger off
31 X120BI1 - ext OC blocking Level trigger off
32 X120BI2 - CB closed Level trigger off
33 X120BI3 - CB opened Level trigger off
3.5.3 Functional diagrams
The functional diagrams describe the default input, output, alarm LED and function-
to-function connections. The default connections can be viewed and changed with
PCM600 according to the application requirements.
The analog channels have fixed connections to the different function blocks inside the
IED’s standard configuration. However, the 12 analog channels available for the
disturbance recorder function are freely selectable as a part of the disturbance
recorder’s parameter settings.
The phase currents to the IED are fed from a current transformer. The residual current
to the IED is fed from either residually connected CTs, an external core balance CT,
neutral CT or internally calculated.
The IED offers six different settings groups which can be set based on individual
needs. Each group can be activated or deactivated using the setting group settings
available in the IED.
Depending on the communication protocol the required function block needs to be
instantiated in the configuration.
3.5.3.1 Functional diagrams for protection
The functional diagrams describe the IEDs protection functionality in detail and
according to the factory set default connections.
Four non-directional overcurrent stages are offered for overcurrent and short-circuit
protection. Three-phase non-directional overcurrent protection, instantaneous stage,
PHIPTOC1 can be blocked by energizing the binary input X120:BI1.