PCM600. The audit trail cannot be reset, but PCM600 Event Viewer can filter data.
Audit trail events can be configured to be visible also in LHMI/WHMI Event list
together with process related events.
To expose the audit trail events through Event list, define the
Authority logging level parameter via Configuration/
Authorization/Security. This exposes audit trail events to all users.
Table 8: Comparison of authority logging levels
Audit trail event Authority logging level
None
Configurati
on change
Setting
group
Setting
group,
control
Settings
edit
All
Configuration change ● ● ● ● ●
Firmware change ● ● ● ● ●
Firmware change fail ● ● ● ● ●
Attached to retrofit test
case
● ● ● ● ●
Removed from retrofit
test case
● ● ● ● ●
Setting group remote ● ● ● ●
Setting group local ● ● ● ●
Control remote ● ● ●
Control local ● ● ●
Test on ● ● ●
Test off ● ● ●
Reset trips ● ● ●
Setting commit ● ●
Time change ●
View audit log ●
Login ●
Logout ●
Password change ●
Firmware reset ●
Violation local ●
Violation remote ●
2.7 Communication
The protection relay supports a range of communication protocols including IEC
61850, IEC 61850-9-2 LE, IEC 60870-5-103, Modbus
®
and DNP3. Profibus DPV1
Section 2 1MRS756378 S
REF615 overview