Table 12: Default connections for binary outputs
Binary output Description
X100-PO1 Close circuit breaker
X100-PO2 Circuit breaker failure protection trip to upstream breaker
X100-PO3 Open circuit breaker/trip coil 1
X100-PO4 Open circuit breaker/trip coil 2
X100-SO1 General start indication
X100-SO2 General operate indication
Table 13: Default connections for LEDs
LED Description
1 Non-directional overcurrent operate
2 Directional or intermittent earth-fault operate
3 Double (cross country) earth-fault or residual overvoltage operate
4 Negative sequence overcurrent or phase discontinuity operate
5 Thermal overload alarm
6 Breaker failure operate
7 Disturbance recorder triggered
8 -
9 Trip circuit supervision alarm
10 Arc protection operate
11 Autoreclose in progress
3.3.2.2 Default disturbance recorder settings
Table 14: Default disturbance recorder analog channels
Channel
Description
1 IL1
2 IL2
3 IL3
4 Io
5 Uo
6 -
7 -
8 -
9 -
10 -
11 -
12 -
1MRS756378 S Section 3
REF615 standard configurations
REF615 51
Application Manual