LED Description
9 Trip circuit supervision alarm
10 Arc protection operate
11 Autoreclose in progress
3.6.2.2 Default disturbance recorder settings
Table 29: Default disturbance recorder analog channels
Channel Description
1 IL1
2 IL2
3 IL3
4 Io
5 -
6 -
7 -
8 -
9 -
10 -
11 -
12 -
Table 30: Default disturbance recorder binary channels
Channel
ID text Level trigger mode
1 PHLPTOC1 - start Positive or Rising
2 PHHPTOC1 - start Positive or Rising
3 PHHPTOC2 - start Positive or Rising
4 PHIPTOC1 - start Positive or Rising
5 NSPTOC1 - start Positive or Rising
6 NSPTOC2 - start Positive or Rising
7 EFLPTOC1 - start Positive or Rising
8 EFHPTOC1 - start Positive or Rising
9 EFIPTOC1 - start Positive or Rising
10 EFLPTOC2 - start Positive or Rising
11 - -
12 PDNSPTOC1 - start Positive or Rising
13 T1PTTR1 - start Positive or Rising
14 CCBRBRF1 - trret Level trigger off
15 CCBRBRF1 - trbu Level trigger off
Table continues on next page
1MRS756378 S Section 3
REF615 standard configurations
REF615 117
Application Manual