3.3.2 Functions
CONDITION MONITORING
AND SUPERVISION
OR
AND
CONTROL AND INDICATION
1)
MEASUREMENT
FEEDER PROTECTION AND CONTROL RELAY STANDARD
CONFIGURATION
PROTECTION
LOCAL HMI
Object Ctrl
2)
Ind
3)
CB
DC
ES
1)
Check availability of binary inputs/outputs
from technical documentation
2)
Control and indication function for
primary object
3)
Status indication function for
primary object
R
L
ClearESC
I
O
Configuration A
System
HMI
Time
Authorization
R
L
ClearESC
I
O
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A
A
REMARKS
Optional
function
No. of
instances
Alternative
function to be
defined when
ordering
OR
Io/Uo
Calculated
value
COMMUNICATION
P
rotocols:
IEC 61850-8-1
Modbus
®
IEC 60870-5-103
DNP3
Interfaces:
Ethernet: TX (RJ45), FX (LC)
Serial: Serial glass fiber (ST),
RS-485, RS-232
Redundant p
rotocols:
HSR
PRP
RSTP
REF615
1 -
- -
- -
- I, Io, Uo
- Limit value supervision
- Symmetrical components
4
1
Analog interface types
1)
Current transformer
Voltage transformer
1)
Conventional transformer inputs
ALSO AVAILABLE
- Disturbance and fault
recorders
- Event log and
recorded data
- Local/Remote push button on LHMI
- Self-supervision
-
Time synchronization: IEEE 1588 v2,
SNTP, IRIG-B
- User management
-
Web HMI
TCS
TCM
OI
79
I2>
46
I2/I1>
46PD
3Ith>F
49F
3I>>>
50P/51P
ARC
50L/50NL
Master Trip
Lockout relay
94/86
Io>
67N-1
Io>>
67N-2
Io>IEF
67NIEF
Uo>
59G
Io>>
51N-2
3I>
51P-1
3I>/Io>BF
51BF/51NBF
3I2f>
68
Yo>
21YN
Po>
32N
OR
3I>>
51P-2
OPTS
OPTM
18×
MAP
MAP
Uo
Uo
Io
Io
A
SOTF
SOTF
GUID-030C217F-7B91-4739-9DAE-90D1E053EB53 V2 EN
Figure 17: Functionality overview for standard configuration A
3.3.2.1 Default I/O connections
Connector pins for each input and output are presented in the IED physical
connections section.
Table 11: Default connections for binary inputs
Binary input
Description
X120-BI1 Blocking of overcurrent instantaneous stage
X120-BI2 Circuit breaker closed position indication
X120-BI3 Circuit breaker open position indication
Section 3 1MRS756378 S
REF615 standard configurations
50 REF615