Table 81: Auxiliary voltage supply
Terminal Description
X100:1 + Input
X100:2 - Input
5.1.3 Binary inputs
The binary inputs can be used, for example, to generate a blocking signal, to unlatch
output contacts, to trigger the disturbance recorder or for remote control of IED
settings.
Binary inputs of slot X110 are available with configurations B, D, E, F, G, H, J, K, L
and N.
Table 82: Binary input terminals X110:1-13 with BIO0005 module
Terminal Description
X110:1 BI1, +
X110:2 BI1, -
X110:3 BI2, +
X110:4 BI2, -
X110:5 BI3, +
X110:6 BI3, -
X110:6 BI4, -
X110:7 BI4, +
X110:8 BI5, +
X110:9 BI5, -
X110:9 BI6, -
X110:10 BI6, +
X110:11 BI7, +
X110:12 BI7, -
X110:12 BI8, -
X110:13 BI8, +
Table 83: Binary input terminals X110:1-10 with BIO0007 module
Terminal
Description
X110:1 BI1, +
X110:5 BI1, -
X110:2 BI2, +
X110:5 BI2, -
X110:3 BI3, +
X110:5 BI3, -
Table continues on next page
1MRS756378 S Section 5
IED physical connections
REF615 385
Application Manual