LED Description
7 Disturbance recorder triggered
8 Circuit breaker condition monitoring alarm
9 Supervision alarm
10 Arc fault detected
11 Autoreclose in progress
3.8.2.2 Default disturbance recorder settings
Table 39: Default disturbance recorder analog channels
Channel Description
1 IL1
2 IL2
3 IL3
4 Io
5 Uo
6 U1
7 U2
8 U3
9 -
10 -
11 -
12 -
Table 40: Default disturbance recorder binary channels
Channel
ID text Level trigger mode
1 DPHLPDOC1 - start Positive or Rising
2 DPHLPDOC2 - start Positive or Rising
3 DPHHPDOC1 - start Positive or Rising
4 PHIPTOC1 - start Positive or Rising
5 NSPTOC1 - start Positive or Rising
6 NSPTOC2 - start Positive or Rising
7 DEFLPDEF1 - start Positive or Rising
EFPADM1 - start
WPWDE1 - start
8 DEFLPDEF2 - start Positive or Rising
EFPADM2 - start
WPWDE2 - start
Table continues on next page
Section 3 1MRS756378 S
REF615 standard configurations
168 REF615
Application Manual