EasyManua.ls Logo

ABB relion REF615 - Page 335

ABB relion REF615
404 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
This signal is not connected in the configuration. This output can be used for sending
a blocking signal to the relevant overcurrent protection stage of the IED at the
infeeding bay.
OR6
B1
B2
B3
B4
B5
B6
O
DPHLPDOC2_START
GUID-7AEA0818-3740-426B-89CB-128FC04D5E3D V1 EN
Figure 507: Upstream blocking logic
The output BLK2H of three-phase inrush detector INRPHAR1 enables either blocking
the function or multiplying the active settings for any of the available overcurrent or
earth-fault function blocks.
INRPHAR1
BLOCK BLK2H
INRPHAR1_BLK2H
GUID-8A44950A-08F8-487A-8285-291BBBFC04C7 V1 EN
Figure 508: Inrush detector function
Two negative-sequence overcurrent protection stages NSPTOC1 and NSPTOC2 are
provided for phase unbalance protection. These functions are used to protect the
feeder against phase unbalance.
NSPTOC1
BLOCK
ENA_MULT
OPERATE
START
NSPTOC2
BLOCK
ENA_MULT
OPERATE
START
NSPTOC1_OPERATE
NSPTOC2_OPERATE
NSPTOC1_START
NSPTOC2_START
GUID-9F91B557-1412-4CB4-897C-9D4BEBCC31F4 V1 EN
Figure 509: Negative-sequence overcurrent protection function
Three stages are provided for directional earth-fault protection. According to the
IED's order code, the directional earth-fault protection method can be based on
conventional directional earth-fault DEFxPDEF only or alternatively used together
with admittance-based earth-fault protection EFPADM or wattmetric-based earth-
fault protection WPWDE or harmonics-based earth-fault protection HAEFPTOC. A
dedicated protection stage INTRPTEF is used either for transient-based earth-fault
protection or for cable intermittent earth-fault protection in compensated networks.
1MRS756378 S Section 3
REF615 standard configurations
REF615 329
Application Manual

Table of Contents

Related product manuals