Measurement function application for a 380kV OHL
SEMOD54481-12 v11
Single line diagram for this application is given in figure 403:
380kV Busbar
380kV OHL
P Q
800/5 A
ANSI09000039-1-en.vsd
380kV 120V
/
3 3
kV
IED
ANSI09000039 V1 EN-US
Figure 403: Single line diagram for 380kV OHL application
In order to monitor, supervise and calibrate the active and reactive power as indicated
in figure
403 it is necessary to do the following:
1. Set correctly CT and VT data and phase angle reference channel PhaseAngleRef
(see Section “Setting of the phase reference channel”) using PCM600 for analog
input channels
2. Connect, in PCM600, measurement function to three-phase CT and VT inputs
3.
Set under General settings parameters for the Measurement function:
• general settings as shown in table
66.
• level supervision of active power as shown in table 67.
• calibration parameters as shown in table 68.
Section 18 1MRK 504 163-UUS A
Monitoring
870 Transformer protection RET670 2.2 ANSI