2.3.2.3 CTRL.Dxxxxx1 Controllable disconnector (1)
Table 8: CTRL.Dxxxxx1 Controllable disconnector (1)
IEC 61850 name SA name Description Values
CTRL.DCCILO1
.EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
.EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
.ItlByPss.stVal ITL_BYPASS Interlocking bypass 1=Bypassed
CTRL.DCCSWI1
.Pos.stSeld SELECTED CB selected 1=Selected
CTRL.DCXSWI1
.BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
.BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
2.3.2.4 CTRL.Dxxxxx2 Controllable disconnector (2)
Table 9: CTRL.Dxxxxx2 Controllable disconnector (2)
IEC 61850 name SA name Description Values
CTRL.DCCILO2
.EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
.EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
.ItlByPss.stVal ITL_BYPASS Interlocking bypass 1=Bypassed
CTRL.DCCSWI2
.Pos.stSeld SELECTED CB selected 1=Selected
CTRL.DCXSWI2
.BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
.BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
2.3.2.5 CTRL.Dxxxxx3 Controllable disconnector (3)
Table 10: CTRL.Dxxxxx3 Controllable disconnector (3)
IEC 61850 name
SA name Description Values
CTRL.DCCILO3
.EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
.EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
.ItlByPss.stVal ITL_BYPASS Interlocking bypass 1=Bypassed
CTRL.DCCSWI3
.Pos.stSeld SELECTED CB selected 1=Selected
CTRL.DCXSWI3
.BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
.BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked