2.5.1.2 LD0.LPHD1 System values
Table 125: LD0.LPHD1 System values
IEC 61850 name SA name Description Values S Arg 1,2,3,4
LD0.LPHD1
.NumCmpChg.stVal - Num.of comp. changes 0…65535 R 0,65535,0,65535
.NumPwrUp.stVal - Num.of power ups 0…65535 R 0,65535,0,65535
.PhyHealth1.stVal Warning Warning code 0…65535 R 0,65535,0,65535
.PhyHealth2.stVal Internal Fault Internal fault code 0…65535 R 0,65535,0,65535
.WacTrg.stVal - Num.of watchdog resets 0…65535 R 0,65535,0,65535
.WrmStr.stVal - Num.of warm starts 0…65535 R 0,65535,0,65535
2.5.1.3 LD0.DNPGGIO1 Active parameter setting group
Table 126: LD0.DNPGGIO1 Active parameter setting group
IEC 61850 name SA name Description Values S Arg 1,2,3,4
LD0.DNPGGIO1
.ActSG.stVal - Active setting group 1…6 R 1,6,1,6
2.5.1.4 LD0.LEDGGIO1 LHMI LED indications (3 states)
Table 127: LD0.LEDGGIO1 LHMI LED indications (3 states)
IEC 61850 name
SA name Description Values S Arg 1,2,3,4
LD0.LEDGGIO1
.ISCSO1.stVal - LED 1 state
0/1/3=Off/Ok/
Alarm R 0,3,0,3
.ISCSO2.stVal - LED 2 state
0/1/3=Off/Ok/
Alarm R 0,3,0,3
.ISCSO3.stVal - LED 3 state
0/1/3=Off/Ok/
Alarm R 0,3,0,3
.ISCSO4.stVal - LED 4 state
0/1/3=Off/Ok/
Alarm R 0,3,0,3
.ISCSO5.stVal - LED 5 state
0/1/3=Off/Ok/
Alarm R 0,3,0,3
.ISCSO6.stVal - LED 6 state
0/1/3=Off/Ok/
Alarm R 0,3,0,3
.ISCSO7.stVal - LED 7 state
0/1/3=Off/Ok/
Alarm R 0,3,0,3
.ISCSO8.stVal - LED 8 state
0/1/3=Off/Ok/
Alarm R 0,3,0,3
.ISCSO9.stVal - LED 9 state
0/1/3=Off/Ok/
Alarm R 0,3,0,3
.ISCSO10.stVal - LED 10 state
0/1/3=Off/Ok/
Alarm R 0,3,0,3
.ISCSO11.stVal - LED 11 state
0/1/3=Off/Ok/
Alarm R 0,3,0,3
Section 2 1MRS757656 A
DNP3 data mappings
54 REM620
Point List Manual