2.3.7 Generic functions
2.3.7.1 LD0.MDSOPT1 Generic operation time supervision
Table 72: LD0.MDSOPT1 Generic operation time supervision
IEC 61850 name SA name Description Values
LD0.MDSOPT1
.OpTmAlm.stVal ALARM Accum.op.time Alarm 1=Alarm
.OpTmWrn.stVal WARNING Accum.op.time Warning 1=Warning
2.3.7.2 LD0.MDSOPT2 Generic operation time supervision
Table 73: LD0.MDSOPT2 Generic operation time supervision
IEC 61850 name SA name Description Values
LD0.MDSOPT2
.OpTmAlm.stVal ALARM Accum.op.time Alarm 1=Alarm
.OpTmWrn.stVal WARNING Accum.op.time Warning 1=Warning
2.3.7.3 LD0.MAPGAPC1 Multipurpose analog protection function (1)
Table 74: LD0.MAPGAPC1 Multipurpose analog protection function (1)
IEC 61850 name
SA name Description Values
LD0.MAPGAPC1
.Op.general OPERATE Stage operate 1 = Operate
.Str.general START Stage start 1 = Start
2.3.7.4 LD0.MAPGAPC2 Multipurpose analog protection function (2)
Table 75: LD0.MAPGAPC2 Multipurpose analog protection function (2)
IEC 61850 name
SA name Description Values
LD0.MAPGAPC2
.Op.general OPERATE Stage operate 1 = Operate
.Str.general START Stage start 1 = Start
2.3.7.5 LD0.MAPGAPC3 Multipurpose analog protection function (3)
Table 76: LD0.MAPGAPC3 Multipurpose analog protection function (3)
IEC 61850 name
SA name Description Values
LD0.MAPGAPC3
.Op.general OPERATE Stage operate 1 = Operate
.Str.general START Stage start 1 = Start
Section 2 1MRS757656 A
DNP3 data mappings
36 REM620