2.3.4.4 LD0.VMMXU1 Three-phase voltage limit supervision
Table 25: LD0.VMMXU1 Three-phase voltage limit supervision
IEC 61850 name SA name Description Values
LD0.VMMXU1
.HiAlm.stVal HIGH_ALARM High alarm 1=Alarm
.HiWrn.stVal HIGH_WARN High warning 1=Warning
.LoAlm.stVal LOW_ALARM Low alarm 1=Alarm
.LoWrn.stVal LOW_WARN Low warning 1=Warning
2.3.4.5 LD0.RESVMMXU1 Residual voltage limit supervision
Table 26: LD0.RESVMMXU1 Residual voltage limit supervision
IEC 61850 name SA name Description Values
LD0.RESVMMXU1
.HiAlm.stVal HIGH_ALARM High alarm 1=Alarm
.HiWrn.stVal HIGH_WARN High warning 1=Warning
2.3.5 Protection functions
2.3.5.1 LD0.LEDPTRC1 Global protection signals
Table 27: LD0.LEDPTRC1 Global protection signals
IEC 61850 name
SA name Description Values
LD0.LEDPTRC1 Global protection signals
.Op.general - -General Operate 1=Operate
.Op.phsA - -phsA Operate 1=Operate
.Op.phsB - -phsB Operate 1=Operate
.Op.phsC - -phsC Operate 1=Operate
.Str.general - -General Start 1=Start
.Str.phsA - -phsA Start 1=Start
.Str.phsB - -phsB Start 1=Start
.Str.phsC - -phsC Start 1=Start
2.3.5.2 LD0.TRPPTRC1 Global conditioning (1)
Table 28: LD0.TRPPTRC1 Global conditioning (1)
IEC 61850 name
SA name Description Values
LD0.TRPPTRC1
.Op.general - Operate input signal 1=Operate
.Tr.general - Trip output signal 1=Trip
1MRS757656 A Section 2
DNP3 data mappings
REM620 25
Point List Manual