2.3.5.8 LD0.DPHHPDOC2 Three-phase directional overcurrent protection -
high stage (2)
Table 34: LD0.DPHHPDOC2 Three-phase directional overcurrent protection - high stage (2)
IEC 61850 name SA name Description Values
LD0.DPHHPTOC2 High stage (2)
.Op.general OPERATE -Operate 1=Operate
.Str.general START -Start 1=Start
2.3.5.9 LD0.PHLPTOC1 Phase overcurrent protection - low stage 1
Table 35: LD0.PHLPTOC1 Phase overcurrent protection - low stage 1
IEC 61850 name SA name Description Values
LD0.PHLPTOC1
.Op.general OPERATE Stage operate 1=Operate
.Str.general START Stage start 1=Start
2.3.5.10 LD0.PHIPTOC1 Phase overcurrent protection - instantaneous stage 1
Table 36: LD0.PHIPTOC1 Phase overcurrent protection - instantaneous stage 1
IEC 61850 name
SA name Description Values
LD0.PHIPTOC1
.Op.general OPERATE Stage operate 1=Operate
.Str.general START Stage start 1=Start
2.3.5.11 LD0.EFLPTOC1 Non-directional earth-fault and sensitive earth-fault
protection - low stage 1
Table 37: LD0.EFLPTOC1 Non-directional earth-fault and sensitive earth-fault protection - low stage 1
IEC 61850 name
SA name Description Values
LD0.EFLPTOC1 Low stage (1)
.Op.general OPERATE -Operate 1=Operate
.Str.general START -Start 1=Start
1MRS757656 A Section 2
DNP3 data mappings
REM620 27
Point List Manual