2.3.3.7 LD0.TCSSCBR2 Trip circuit supervision (2)
Table 21: LD0.TCSSCBR2 Trip circuit supervision (2)
IEC 61850 name SA name Description Values
LD0.TCSSCBR2
.CirAlm.stVal ALARM Supervision alarm 1=Alarm
2.3.4 Metering and measurand functions
2.3.4.1 LD0.CMMXU1 Phase currents (1) limit supervision
Table 22: LD0.CMMXU1 Phase currents (1) limit supervision
IEC 61850 name SA name Description Values
LD0.CMMXU1
.HiAlm.stVal HIGH_ALARM High alarm 1=Alarm
.HiWrn.stVal HIGH_WARN High warning 1=Warning
.LoAlm.stVal LOW_ALARM Low alarm 1=Alarm
.LoWrn.stVal LOW_WARN Low warning 1=Warning
2.3.4.2 LD0.CMMXU2 Phase currents (2) limit supervision
Table 23: LD0.CMMXU2 Phase currents (2) limit supervision
IEC 61850 name
SA name Description Values
LD0.CMMXU2
.HiAlm.stVal HIGH_ALARM High alarm 1=Alarm
.HiWrn.stVal HIGH_WARN High warning 1=Warning
.LoAlm.stVal LOW_ALARM Low alarm 1=Alarm
.LoWrn.stVal LOW_WARN Low warning 1=Warning
2.3.4.3 LD0.RESCMMXU1 Residual current limit supervision
Table 24: LD0.RESCMMXU1 Residual current limit supervision
IEC 61850 name
SA name Description Values
LD0.RESCMMXU1
.HiAlm.stVal HIGH_ALARM High alarm 1=Alarm
.HiWrn.stVal HIGH_WARN High warning 1=Warning
Section 2 1MRS757656 A
DNP3 data mappings
24 REM620
Point List Manual