2.5.4 Metering and measurand functions
2.5.4.1 LD0.CMMXU1 Phase currents (1)
Table 144: LD0.CMMXU1 Phase currents (1)
IEC 61850 name SA name Description Values S Arg 1,2,3,4
LD0.CMMXU1 Phase-to-ground current
.A.phsA.instCVal.mag I_INST_A -phsA magnitude 0.00..40.0 [xIn] R 0,40,0,4000
.A.phsB.instCVal.mag I_INST_B -phsB magnitude 0.00..40.0 [xIn] R 0,40,0,4000
.A.phsC.instCVal.mag I_INST_C -phsC magnitude 0.00..40.0 [xIn] R 0,40,0,4000
2.5.4.2 LD0.RESCMMXU1 Residual current (1)
Table 145: LD0.RESCMMXU1 Residual current (1)
IEC 61850 name SA name Description Values S Arg 1,2,3,4
LD0.RESCMMXU1
.A.res.instCVal.mag I0_INST Residual current 0.00..40.0 [xIn] R 0,40,0,4000
2.5.4.3 LD0.CSMSQI1 Sequence of currents
Table 146: LD0.CSMSQI1 Sequence of currents
IEC 61850 name
SA name Description Values S Arg 1,2,3,4
LD0.CSMSQI1 Sequence of currents
.SeqA.c1.instCVal.mag I1_INST -Positive magnitude 0.00..40.0 [xIn] R 0,40,0,4000
.SeqA.c2.instCVal.mag I2_INST -Negative magnitude 0.00..40.0 [xIn] R 0,40,0,4000
.SeqA.c3.instCVal.mag I3_INST -Zero magnitude 0.00..40.0 [xIn] R 0,40,0,4000
2.5.4.4 LD0.VMMXU1 Voltage measurement
Table 147: LD0.VMMXU1 Voltage measurement
IEC 61850 name
SA name Description Values S Arg 1,2,3,4
LD0.VMMXU1.PhV Phase-to-ground voltage
.phsA.cVal.mag U_DB_A -phsA magnitude
0.00…4.00
[xUn] R 0,4,0,400
.phsB.cVal.mag U_DB_B -phsB magnitude
0.00…4.00
[xUn] R 0,4,0,400
.phsC.cVal.mag U_DB_C -phsC magnitude
0.00…4.00
[xUn] R 0,4,0,400
LD0.VMMXU1.PPV Phase-to-phase voltage
Table continues on next page
1MRS757656 A Section 2
DNP3 data mappings
REM620 59
Point List Manual

Table of Contents