2.4.3.2 LD0.SSCBR2 Reset signals of CB condition monitoring
Table 114: LD0.SSCBR2 Reset signals of CB condition monitoring
IEC 61850 name SA name Description Type
LD0.SSCBR2
.RsAccAPwr.Oper.ctlVal RST_IPOW Reset accum. energy On
.RsCBWear.Oper.ctlVal RST_CB_WEAR Reset CB life and op. counter On
.RsSprChaTm.Oper.ctlVal RST_SPR_T Reset spring charge alarm On
.RsTrvTm.Oper.ctlVal RST_TRV_T Reset travel time alarm On
2.4.4 Metering and measurand functions
2.4.4.1 LD0.PEMMXU1 Reset accumulated energy values
Table 115: LD0.PEMMXU1 Reset accumulated energy values
IEC 61850 name SA name Description Type
LD0.PEMMXU1
.SupDmdRs.Oper.ctlVal RSTACM Reset accum. energy On
2.4.5 Protection related functions
2.4.5.1 DR.RDRE1 Disturbance recorder
Table 116: DR.RDRE1 Disturbance recorder
IEC 61850 name
SA name Description Type
DR.RDRE1
.MemClr.Oper.ctlVal - Clear all records On
.RcdTrg.Oper.ctlVal - Trig recording On
2.4.6 Generic functions
2.4.6.1 LD0.SPCGGIO1 Multipurpose binary outputs (1)
The binary outputs can be configured either as pulse- or persistent-type outputs. Pulse-
type outputs are triggered with the write value "1". Persistent-type outputs can be
written with both values "1" and "0" values. The setting mode "toggled" for local
operation corresponds to "persistent" for remote operation.
1MRS757656 A Section 2
DNP3 data mappings
REM620 49
Point List Manual