Function block ME201
FMMXU1
RDRE1
● = available in the device variant, o = optionally available in the device variant
2.3 Binary inputs
Table 3: Explanations of the binary input table columns
Column name Description
IEC 61850
name
Original IED data object identification. Described in the IEC 61850 format as
Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical
Node is the same as the application function block name.
SA name The signal may have a defined label that is visible, for example, in the Application
Configuration tool in PCM600.
Description Short description of the signal. See the technical manual for more information.
Value Meaning of the input states.
2.3.1 System functions
2.3.1.1 CTRL.LLN0 Local/remote state (also present in DNP IIN-bits)
Table 4: CTRL.LLN0 Local/remote state (also present in DNP IIN-bits)
IEC 61850 name
SA name Description Values
CTRL.LLN0
.Loc.stVal Remote/Local state 0/1=Rem/Loc
2.3.1.2 LD0.LLN0 Settings supervision
Table 5: LD0.LLN0 Settings supervision
IEC 61850 name
SA name Description Values
LD0.LLN0
.SetChg.stVal - Settings changed 1=Changed
.SetSeld.stVal - Settings reserved 1=Reserved
Section 2 1MRS757656 A
DNP3 data mappings