EasyManua.ls Logo

ABB REM620 - Ctrl.dxxxxx4 Controllable Disconnector (4); Ctrl.exxxxx1 Controllable Earth Switch (1); Ctrl.exxxxx2 Controllable Earth Switch (2)

ABB REM620
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.3.2.6 CTRL.Dxxxxx4 Controllable disconnector (4)
Table 11: CTRL.Dxxxxx4 Controllable disconnector (4)
IEC 61850 name SA name Description Values
CTRL.DCCILO4
.EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
.EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
.ItlByPss.stVal ITL_BYPASS Interlocking bypass 1=Bypassed
CTRL.DCCSWI4
.Pos.stSeld SELECTED CB selected 1=Selected
CTRL.DCXSWI4
.BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
.BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
2.3.2.7 CTRL.Exxxxx1 Controllable earth switch (1)
Table 12: CTRL.Exxxxx1 Controllable earth switch (1)
IEC 61850 name SA name Description Values
CTRL.ESCILO1
.EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
.EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
.ItlByPss.stVal ITL_BYPASS Interlocking bypass 1=Bypassed
CTRL.ESCSWI1
.Pos.stSeld SELECTED CB selected 1=Selected
CTRL.ESXSWI1
.BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
.BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
2.3.2.8 CTRL.Exxxxx2 Controllable earth switch (2)
Table 13: CTRL.Exxxxx2 Controllable earth switch (2)
IEC 61850 name
SA name Description Values
CTRL.ESCILO2
.EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
.EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
.ItlByPss.stVal ITL_BYPASS Interlocking bypass 1=Bypassed
CTRL.ESCSWI2
.Pos.stSeld SELECTED CB selected 1=Selected
CTRL.ESXSWI2
.BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
.BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
1MRS757656 A Section 2
DNP3 data mappings
REM620 21
Point List Manual

Table of Contents