2.3.2.6 CTRL.Dxxxxx4 Controllable disconnector (4)
Table 11: CTRL.Dxxxxx4 Controllable disconnector (4)
IEC 61850 name SA name Description Values
CTRL.DCCILO4
.EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
.EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
.ItlByPss.stVal ITL_BYPASS Interlocking bypass 1=Bypassed
CTRL.DCCSWI4
.Pos.stSeld SELECTED CB selected 1=Selected
CTRL.DCXSWI4
.BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
.BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
2.3.2.7 CTRL.Exxxxx1 Controllable earth switch (1)
Table 12: CTRL.Exxxxx1 Controllable earth switch (1)
IEC 61850 name SA name Description Values
CTRL.ESCILO1
.EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
.EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
.ItlByPss.stVal ITL_BYPASS Interlocking bypass 1=Bypassed
CTRL.ESCSWI1
.Pos.stSeld SELECTED CB selected 1=Selected
CTRL.ESXSWI1
.BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
.BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
2.3.2.8 CTRL.Exxxxx2 Controllable earth switch (2)
Table 13: CTRL.Exxxxx2 Controllable earth switch (2)
IEC 61850 name
SA name Description Values
CTRL.ESCILO2
.EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
.EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
.ItlByPss.stVal ITL_BYPASS Interlocking bypass 1=Bypassed
CTRL.ESCSWI2
.Pos.stSeld SELECTED CB selected 1=Selected
CTRL.ESXSWI2
.BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
.BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
1MRS757656 A Section 2
DNP3 data mappings
REM620 21