2.3.5.3 LD0.TRPPTRC2 Global conditioning (2)
Table 29: LD0.TRPPTRC2 Global conditioning (2)
IEC 61850 name SA name Description Values
.Op.general - Operate input signal 1=Operate
.Tr.general - Trip output signal 1=Trip
2.3.5.4 LD0.DEFLPDEF1 Directional earth-fault protection - low stage 1
Table 30: LD0.DEFLPDEF1 Directional earth-fault protection - low stage 1
IEC 61850 name SA name Description Values
LD0.DEFLPTOC1 Low stage (1)
.Op.general OPERATE -Operate 1=Operate
.Str.general START -Start 1=Start
2.3.5.5 LD0.DEFHPDEF1 Directional earth-fault protection - high stage 1
Table 31: LD0.DEFHPDEF1 Directional earth-fault protection - high stage 1
IEC 61850 name
SA name Description Values
LD0.DEFHPTOC1 High stage (1)
.Op.general OPERATE -Operate 1=Operate
.Str.general START -Start 1=Start
2.3.5.6 LD0.DPHLPDOC1 Three-phase directional overcurrent protection -
low stage (1)
Table 32: LD0.DPHLPDOC1 Three-phase directional overcurrent protection - low stage (1)
IEC 61850 name
SA name Description Values
LD0.DPHLPTOC1 Low stage (1)
.Op.general OPERATE -Operate 1=Operate
.Str.general START -Start 1=Start
2.3.5.7 LD0.DPHHPDOC1 Three-phase directional overcurrent protection -
high stage (1)
Table 33: LD0.DPHHPDOC1 Three-phase directional overcurrent protection - high stage (1)
IEC 61850 name
SA name Description Values
LD0.DPHHPTOC1 High stage (1)
.Op.general OPERATE -Operate 1=Operate
.Str.general START -Start 1=Start
Section 2 1MRS757656 A
DNP3 data mappings
26 REM620
Point List Manual