Operation mode 3I
0
· 3V
0
· cosφ
1. Set the polarizing voltage to 1.2 · VNRelPU and the phase angle between voltage and
current to the set characteristic angle (RCADir), the current lagging the voltage.
2. Measure that the operate power is equal to the SN_PU setting for the set directional
element.
Note that for pick-up, both the injected current and voltage must be greater than the
set values INRelPU and VNRelPU respectively.
The function activates the BFI_3P and STDIRIN outputs.
3. Measure with angles j = RCADir +/- 45° that the measuring element operates when
3I
0
· 3V
0
· cos (RCADir - j) = 3I0 · 3V0 · cos(+/-45) = SN_PU.
4. Compare the result with the set value. Take the set characteristic into consideration,
see figure
10 and figure 11.
1MRK 505 293-UUS A Section 6
Testing functionality
55
Commissioning manual

Table of Contents

Other manuals for ABB REQ650

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REQ650 and is the answer not in the manual?

ABB REQ650 Specifications

General IconGeneral
BrandABB
ModelREQ650
CategoryProtection Device
LanguageEnglish

Related product manuals