EasyManua.ls Logo

ABB REQ650 - Page 166

ABB REQ650
340 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
High impedance earthed systems
In high impedance earthed systems, earth-faults cause a voltage increase in the non-
faulty phases. OV2PTOV can be used to detect such faults. The setting must be above
the highest occurring "normal" voltage and below the lowest occurring voltage during
faults. A metallic single-phase earth-fault causes the non-faulted phase voltages to
increase a factor of √3.
The following settings can be done for Two step overvoltage protection
GlobalBaseSel: Selects the global base value group used by the function to define
(IBase), (UBase) and (SBase).
ConnType: Sets whether the measurement shall be phase-to-earth fundamental value,
phase-to-phase fundamental value, phase-to-earth RMS value or phase-to-phase
RMS value.
Operation: Off/On .
OV2PTOV measures the phase-to-earth voltages, or phase-to-phase voltages as
selected. The function will operate if the voltage gets higher than the set percentage of
the global set base voltage UBase. This means operation for phase-to-earth voltage
over:
( )
(%)
3
UBase kV
U > ×
IEC09000054 V1 EN (Equation 69)
and operation for phase-to-phase voltage over:
U (%) UBase(kV)> ×
EQUATION1993 V1 EN (Equation 70)
Characteristic1: This parameter gives the type of time delay to be used. The setting
can be. Definite time/Inverse Curve A/Inverse Curve B/Inverse Curve C. The choice
is highly dependent of the protection application.
OpModen: This parameter describes how many of the three measured voltages that
should be above the set level to give operation for step n (n=step 1 and 2). The setting
can be 1 out of 3, 2 out of 3 or 3 out of 3. In most applications it is sufficient that one
phase voltage is high to give operation. If the function shall be insensitive for single
phase-to-earth faults 3 out of 3 can be chosen, because the voltage will normally rise
in the non-faulted phases at single phase-to-earth faults.
Un>: Set overvoltage operating value for step n (n=step 1 and 2), given as % of the
global parameter UBase. The setting is highly dependent of the protection application.
Here it is essential to consider the Maximum voltage at non-faulted situations.
Normally this voltage is less than 110% of nominal voltage.
tn: time delay for step n (n=step 1 and 2), given in s. The setting is highly dependent
of the protection application. In many applications the protection function has the task
Section 7 1MRK 505 291-UEN A
Voltage protection
160
Application manual

Table of Contents

Other manuals for ABB REQ650

Related product manuals