10.3.2.4 Blocking of the autorecloser
Auto-Reclose attempts are expected to take place only in the event of transient faults
on the own line. The Auto-Recloser must be blocked for the following conditions:
Tripping from Delayed Distance protection zones
Tripping from Back-up protection functions
Tripping from Breaker failure function
Intertrip received from remote end Breaker failure function
Busbar protection tripping
Depending of the starting principle (General Trip or only Instantaneous trip) adopted
above the delayed and back-up zones might not be required. Breaker failure local and
remote must however always be connected.
10.3.2.5 Control of the auto-reclosing open time for shot 1
Up to four different time settings can be used for the first shot, and one extension time.
There are separate settings for single- and three-phase auto-reclosing open time, t1
1Ph, t1 3Ph. If no particular input signal is applied, and an autoreclosing program with
single-phase reclosing is selected, the auto-reclosing open time t1 1Ph will be used. If
input signal TR3P is activated in connection with start, the auto-reclosing open time
for three-phase reclosing is used.
An auto-reclosing open time extension delay, tExtended t1, can be added to the normal
shot 1 delay. It is intended to come into use if the communication channel for
permissive line protection is lost. In such a case there can be a significant time
difference in fault clearance at the two ends of the line. A longer “auto-reclosing open
time” can then be useful. This extension time is controlled by setting parameter
Extended t1 = On and the input PLCLOST.
10.3.2.6 Long trip signal
In normal circumstances the trip command resets quickly due to fault clearing. The
user can set a maximum trip pulse duration tTrip. When trip signals are longer, the
auto-reclosing open time is extended by tExtended t1. If Extended t1 = Off, a long trip
signal interrupts the reclosing sequence in the same way as a signal to input INHIBIT.
10.3.2.7 Reclosing programs
The maximum number of reclosing shots in an auto-reclosing cycle is selected by the
setting parameter NoOfShots. The type of reclosing used at the first reclosing shot is
set by parameter FirstShot. The first alternative is three-phase reclosing. The other
alternatives include some single-phase or two-phase reclosing. Usually there is no
two-phase tripping arranged, and then there will be no two-phase reclosing.
Section 10 1MRK 505 291-UEN A
Control
216
Application manual

Table of Contents

Other manuals for ABB REQ650

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REQ650 and is the answer not in the manual?

ABB REQ650 Specifications

General IconGeneral
BrandABB
ModelREQ650
CategoryProtection Device
LanguageEnglish

Related product manuals