Figure 77: Operating principle of the trip-circuit supervision without an external
resistor. The circuit breaker open indication is set to block TCSSCBR
when the circuit breaker is open.
Trip-circuit supervision and other trip contacts
It is typical that the trip circuit contains more than one trip contact in parallel, for
example in transformer feeders where the trip of a Buchholz relay is connected in
parallel with the feeder terminal and other relays involved.
GUID-7264738C-F9D7-48F0-B6FC-F85FD10D5B84 V1 EN
Figure 78: Constant test current flow in parallel trip contacts and trip-circuit
supervision