REQ650 (A01)
Z
SC
: High
Ph – ph short circuit
IEC10000149-1-en.vsd
IEC10000149 V1 EN
Figure 15: Fault for step 2 setting
In case of a three-phase short circuit in zone 1 reach in the shortest line from the busbar
as shown in figure
16, the current to the protection is I = 1.8 kA.
Section 3 1MRK 505 291-UEN A
REQ650 setting examples
50
Application manual