The start and trip LEDs are configured via the disturbance recorder.
The yellow and red status LEDs are configured in the disturbance
recorder function, DRPRDRE, by connecting a start or trip signal
from the actual function to a BxRBDR binary input function block
using the PCM600 and configure the setting to Off, Start or Trip for
that particular signal.
Table 11: Ready LED (green)
LED state Description
Off Auxiliary supply voltage is disconnected.
On Normal operation.
Flashing Internal fault has occurred.
Table 12: Start LED (yellow)
LED state Description
Off Normal operation.
On A protection function has started and an indication message is displayed.
The start indication is latching and must be reset via communication or
by pressing
.
Flashing
A flashing yellow LED has a higher priority than a steady yellow LED.
The IED is in test mode and protection functions are blocked.
The indication disappears when the IED is no longer in test mode and
blocking is removed.
Table 13: Trip LED (red)
LED state
Description
Off Normal operation.
On A protection function has tripped and an indication message is displayed.
The trip indication is latching and must be reset via communication or
by pressing
.
Alarm indicators
The 15 programmable three-color LEDs are used for alarm indication. An individual
alarm/status signal, connected to any of the LED function blocks, can be assigned to
one of the three LED colors when configuring the IED.
1MRK 505 291-UEN A Section 5
Local human-machine interface
81