Object type Addr IEC 61850 name SA name Description Values
1 840 .Op.general OPERATE General operate 1=Operate
1 841 .Op.phsA phase A operate 1=Operate
1 842 .Op.phsB phase B operate 1=Operate
1 843 .Op.phsC phase C operate 1=Operate
2.3.7 LD0.FDPHLPDOC2 FA - Directional phase overcurrent
protection, low stage (2)
Table 9: LD0.FDPHLPDOC2 FA - Directional phase overcurrent protection, low stage (2)
Object type Addr IEC 61850 name SA name Description Values
LD0.FDPHLPTOC2
1 852 .Str.general START General start 1=Start
1 853 .Str.phsA phase A start 1=Start
1 854 .Str.phsB phase B start 1=Start
1 855 .Str.phsC phase C start 1=Start
1 848 .Op.general OPERATE General operate 1=Operate
1 849 .Op.phsA phase A operate 1=Operate
1 850 .Op.phsB phase B operate 1=Operate
1 851 .Op.phsC phase C operate 1=Operate
2.3.8 LD0.DPHHPDOC1 Three-phase directional overcurrent
protection, high stage (1)
Table 10: LD0.DPHHPDOC1 Three-phase directional overcurrent protection, high stage (1)
Object type
Addr IEC 61850 name SA name Description Values
LD0.DPHHPTOC1
1 836 .Str.general START General start 1=Start
1 837 .Str.phsA phase A start 1=Start
1 838 .Str.phsB phase B start 1=Start
1 839 .Str.phsC phase C start 1=Start
1 832 .Op.general OPERATE General operate 1=Operate
1 833 .Op.phsA phase A operate 1=Operate
1 834 .Op.phsB phase B operate 1=Operate
1 835 .Op.phsC phase C operate 1=Operate