2.3.67 LD0.VMMXU1 Phase voltage limit supervision (1)
Table 69: LD0.VMMXU1 Phase voltage limit supervision (1)
Object type Addr IEC 61850 name SA name Description Values
LD0.VMMXU1
1 4715 .HiAlm.stVal HIGH_ALARM High alarm 1=Alarm
1 4716 .HiWrn.stVal HIGH_WARN High warning 1=Warning
1 4717 .LoAlm.stVal LOW_ALARM Low alarm 1=Alarm
1 4718 .LoWrn.stVal LOW_WARN Low warning 1=Warning
2.3.68 LD0.VMMXU2 Phase voltage limit supervision (2)
Table 70: LD0.VMMXU2 Phase voltage limit supervision (2)
Object type Addr IEC 61850 name SA name Description Values
LD0.VMMXU2
1 4719 .HiAlm.stVal HIGH_ALARM High alarm 1=Alarm
1 4720 .HiWrn.stVal HIGH_WARN High warning 1=Warning
1 4721 .LoAlm.stVal LOW_ALARM Low alarm 1=Alarm
1 4722 .LoWrn.stVal LOW_WARN Low warning 1=Warning
2.3.69 LD0.MVGAPC1 Multipurpose binary inputs (1)
Table 71: LD0.MVGAPC1 Multipurpose binary inputs (1)
Object type
Addr IEC 61850 name SA name Description Values
LD0.MVGAPC1
1 230 .Q1.stVal Input 1 0/1=Off/On
1 231 .Q2.stVal Input 2 0/1=Off/On
1 232 .Q3.stVal Input 3 0/1=Off/On
1 233 .Q4.stVal Input 4 0/1=Off/On
1 234 .Q5.stVal Input 5 0/1=Off/On
1 235 .Q6.stVal Input 6 0/1=Off/On
1 236 .Q7.stVal Input 7 0/1=Off/On
1 237 .Q8.stVal Input 8 0/1=Off/On
Section 2 1MRS757824 C
IEC 60850-5-101/104 data mappings
34 Recloser Protection and Control RER615
Point List Manual