Table 99: Supported ASDU types in monitoring direction
Object
type
Description IEC 60870-5-101/104 ASDU alternatives
Interrogated Change event
ASDU Type string ASDU Type string
30 Integrated totals 15 M_IT_NA_1 16
M_IT_TA_1
1)
37
M_IT_TB_1
2)
1) Requires setting parameter
Time Format
to be in mode “Short 24 bits”
2) Requires setting parameter
Time Format
to be in mode “Full 56 bits”
2.5.2 CTRL.CBCSWI1 Operation counter
Table 100: CTRL.CBCSWI1 Operation counter
Object type Addr IEC 61850 name SA name Description Values
CTRL.CBSWI1
30 .OpCntRs.stVal CB1 op. counter 0…65535
2.5.3 LD0.PEMMTR1 Three-phase energy values (1)
Table 101: LD0.PEMMTR1 Three-phase energy values (1)
Object type
Addr IEC 61850 name SA name Description Values
LD0.PEMMTR1
30 14000 .SupWh.actVal Reverse active energy 0...1E10 [Kwh]
30 14001 .SupVArh.actVal Reverse reactive energy 0...1E10 [kVAr]
30 14002 .DmdWh.actVal Forward active energy 0...1E10 [Kwh]
30 14003 .DmdVArh.actVal Forward reactive energy 0...1E10 [kVAr]
2.6 Controls
2.6.1 Supported ASDU types
The Object type column contains an internal type identification for the data objects.
The internal object types appear in the protocol as standard IEC 60870-5-101/104
ASDU data types.
Table 102: Supported ASDU types in control direction
Object type
Description ASDU Type string
50 Single bit control 45 C_SC_NA_1
51 Double bit control 47 C_DC_NA_1
Section 2 1MRS757824 C
IEC 60850-5-101/104 data mappings
46 Recloser Protection and Control RER615
Point List Manual