2.3.32 LD0.PHPTOV2 Phase overvoltage protection (2)
Table 34: LD0.PHPTOV2 Phase overvoltage protection (2)
Object type Addr IEC 61850 name SA name Description Values
LD0.PHPTOV2
1 1031 .Str.general START General start 1=Start
1 1032 .Str.phsA phase A start 1=Start
1 1033 .Str.phsB phase B start 1=Start
1 1034 .Str.phsC phase C start 1=Start
1 1027 .Op.general OPERATE General operate 1=Operate
1 1028 .Op.phsA phase A operate 1=Operate
1 1029 .Op.phsB phase B operate 1=Operate
1 1030 .Op.phsC phase C operate 1=Operate
2.3.33 LD0.PHPTOV3 Phase overvoltage protection (3)
Table 35: LD0.PHPTOV3 Phase overvoltage protection (3)
Object type Addr IEC 61850 name SA name Description Values
LD0.PHPTOV3
1 1039 .Str.general START General start 1=Start
1 1040 .Str.phsA phase A start 1=Start
1 1041 .Str.phsB phase B start 1=Start
1 1042 .Str.phsC phase C start 1=Start
1 1035 .Op.general OPERATE General operate 1=Operate
1 1036 .Op.phsA phase A operate 1=Operate
1 1037 .Op.phsB phase B operate 1=Operate
1 1038 .Op.phsC phase C operate 1=Operate
2.3.34 LD0.PSPTUV1 Positive-sequence undervoltage protection
(1)
Table 36: LD0.PSPTUV1 Positive-sequence undervoltage protection (1)
Object type
Addr IEC 61850 name SA name Description Values
LD0.PSPTUV1
1 1077 .Str.general START General start 1=Start
1 1073 .Op.general OPERATE General operate 1=Operate
1MRS757824 C Section 2
IEC 60850-5-101/104 data mappings
Recloser Protection and Control RER615 25
Point List Manual