2.4.6 LD0.SSCBR1 Circuit breaker condition monitoring (1)
Table 86: LD0.SSCBR1 Circuit breaker condition monitoring (1)
Object type Addr IEC 61850 name SA name Description Values
LD0.SSCBR1
20 10131 .AccAPwrPhA.mag - Iyt value, phase A 0...1e6
20 10132 .AccAPwrPhB.mag - Iyt value, phase B 0...1e6
20 10133 .AccAPwrPhC.mag - Iyt value, phase C 0...1e6
21 10134 .InaTmdCnt.stVal INA_DAYS CB inactive days 0...9999
21 10135 .OpCnt.stVal NO_OPR CB op.counter 0...99999
21 10136 .RmnLifPhA.stVal CB_LIFE_A Remaining life, phase A -9999...9999
21 10137 .RmnLifPhB.stVal CB_LIFE_B Remaining life, phase B -9999...9999
21 10138 .RmnLifPhC.stVal CB_LIFE_C Remaining life, phase C -9999...9999
20 10139 .TmmsCls.mag.f - Close travel time 0...60000
20 10140 .TmmsOpn.mag.f - Open travel time 0...60000
20 10141 .TmsSprCha.mag.f - Spring charge time 0...99.99
2.4.7 LD0.MDSOPT1 Generic operation time supervision (1)
Table 87: LD0.MDSOPT1 Generic operation time supervision (1)
Object type
Addr IEC 61850 name SA name Description Values
LD0.MDSOPT1
21 8512 .stVal OPR_TIME Operating days (hours ×
0.0417)
0…12150 [days]
20 - .stVal OPR_TIME Operating hours 0…299999 [hours]
22 - .stVal OPR_TIME Operating days (hours ×
0.0417)
0…12150 [days]
2.4.8 LD0.CMMXU1 Phase current measurement (1)
Table 88: LD0.CMMXU1 Phase current measurement (1)
Object type
Addr IEC 61850 name SA name Description Values
LD0.CMMXU1.A Phase current 1
20 8000 .cVal.phsA.mag I_ISNT_A - phase A magnitude 0...40.00 [xln]
20 8001 .cVal.phsB.mag I_INST_B - phase B magnitude 0...40.00 [xln]
20 8002 .cVal.phsC.mag I_INST_C - phase C magnitude 0...40.00 [xln]
1MRS757824 C Section 2
IEC 60850-5-101/104 data mappings
Recloser Protection and Control RER615 41
Point List Manual