2.4.17 LD0.LEDGGIO1 LED states (1)
Table 97: LD0.LEDGGIO1 LED states (1)
Object type Addr IEC 61850 name SA name Description Values
LD0.LEDGGIO1
21 8501 .ISC01.stVal 0=Off; 1=Alarm; 2=Warning 0...2
21 8502 .ISC02.stVal 0=Off; 1=Alarm; 2=Warning 0...2
21 8503 .ISC03.stVal 0=Off; 1=Alarm; 2=Warning 0...2
21 8504 .ISC04.stVal 0=Off; 1=Alarm; 2=Warning 0...2
21 8505 .ISC05.stVal 0=Off; 1=Alarm; 2=Warning 0...2
21 8506 .ISC06.stVal 0=Off; 1=Alarm; 2=Warning 0...2
21 8507 .ISC07.stVal 0=Off; 1=Alarm; 2=Warning 0...2
21 8508 .ISC08.stVal 0=Off; 1=Alarm; 2=Warning 0...2
21 8509 .ISC09.stVal 0=Off; 1=Alarm; 2=Warning 0...2
21 8510 .ISC10.stVal 0=Off; 1=Alarm; 2=Warning 0...2
21 8511 .ISC11.stVal 0=Off; 1=Alarm; 2=Warning 0...2
2.4.18 LD0.FLTMSTA1 Fault record data (1)
Table 98: LD0.FLTMSTA1 Fault record data (1)
Object type
Addr IEC 61850 name SA name Description Values
LD0.FLTMSTA1
20 8024 .OpCnt.stVal Fault record number 0...999999
20 12100 .ProFcn.stVal Protective function See the technical
manual.
20 12000 .StrDur.mag Start duration 0...100.00 [%]
20 12101 .OpTm.mag Operation time 0.000...999999.999 [s]
20 12102 .ActSG.stVal Active setting group 1...6
20 12103 .ShotPntr.stVal AR shot pointer 0...7
20 12104 .FltDiskm.mag Fault distance 0...9999.99 [pu]
20 12015 .MaxAmpsA.mag Max phsA current 0...50.0 [xIn]
20 12016 .MaxAmpsB.mag Max phsB current 0...50.0 [xIn]
20 12017 .MaxAmpsC.mag Max phsC current 0...50.0 [xIn]
20 12018 .MaxAmpsN.mag Max residual current 0...50.0 [xIn]
20 12019 .AmpsA.mag PhsA current 0...50.0 [xIn]
20 12020 .AmpsB.mag PhsB current 0...50.0 [xIn]
20 12021 .AmpsC.mag PhsC current 0...50.0 [xIn]
20 12022 .AmpsN.mag Residual current 0...50.0 [xIn]
20 12023 .AmpsNClc.mag Residual current (calc) 0...50.0 [xIn]
20 12024 .AmpsPsSeq.mag Positive seq. current 0...50.0 [xIn]
20 12025 .AmpsNgSeq.mag Negative seq. current 0...50.0 [xIn]
Table continues on next page
Section 2 1MRS757824 C
IEC 60850-5-101/104 data mappings
44 Recloser Protection and Control RER615
Point List Manual