Object type Addr IEC 61850 name SA name Description Values
1 47 .Op.phsB - phsB Operate 1=Operate
1 48 .Op.phsC - phsC Operate 1=Operate
1 49 .Op.neut - neut Operate 1=Operate
2.4 Measurands
2.4.1 Supported ASDU types
The Object type column contains an internal type identification for the data objects.
Internal object types in turn can be configured into different IEC 60870-5-101/104
ASDU data types.
For measurand values, the object type code also reflects which value coding
variation the object has as default.
Table 81: Supported ASDU types in monitoring direction
Object
type
Description IEC 60870-5-101/104 ASDU alternatives
Interrogated Change event
ASDU Type string ASDU Type string
20 Measurand,
floating point
13 M_ME_NC_1 14 M_ME_TC_1
1)2)
36
M_ME_TF_1
2)3)
21 Measurand,
normalized
9 M_ME_NA_1 10
M_ME_TA_1
1)2)
34 M_ME_TD_1
2)3)
22 Measurand,
scaled value
11 M_ME_NB_1 12
M_ME_TB_1
1)2)
35
M_ME_TE_1
2)3)
1) Requires setting parameter
Time Format
to be in mode “Short 24 bits”
2) The stack supports point-dependent value format changing between all three measurand formats. In
PCM600 each measurand object occurs in three interchangable format instances.
3) Requires setting parameter
Time Format
to be in mode “Full 56 bits”
2.4.2 General device data
Table 82: General device data
Object type
Addr IEC 61850 name SA name Description Values
CTRL.LLN0
20 10002 LocRem.stVal Local/Remote state analog 0=Off; 1=Local;
2=Remote; 3=Station
LD0.LLN0
21 40000 .ActSG.stVal Active setting group 1...6
DR.RDRE1
Table continues on next page
1MRS757824 C Section 2
IEC 60850-5-101/104 data mappings
Recloser Protection and Control RER615 39
Point List Manual