2.3.63 LD0.MDSOPT1 Generic operation time supervision (1)
Table 65: LD0.MDSOPT1 Generic operation time supervision (1)
Object type Addr IEC 61850 name SA name Description Values
LD0.MDSOPT1
1 971 OpTmWrn.stVal WARNING Op. time warning 1=Warning
1 972 OpTmAlm.stVal ALARM Op. time alarm 2=Alarm
2.3.64 LD0.PHSVPR1 Voltage presence supervision (1)
Table 66: LD0.PHSVPR1 Voltage presence supervision (1)
Object type Addr IEC 61850 name SA name Description Values
LD0.PHSVPR1
1 210 .VLiv.stVal U_LIVE High voltage presence 1=High voltage
1 211 .VLivPhsA.stVal U_A_AB_LIVE High phsA or phsAB voltage 1=High voltage
1 212 .VLivPhsB.stVal U_B_BC_LIVE High phsB or phsBC voltage 1=High voltage
1 213 .VLivPhsC.stVal U_C_CA_LIVE High phsC or phsCA voltage 1=High voltage
1 214 .VDea.stVal U_DEAD Low voltage presence 1=Low voltage
1 215 .VDeaPhsA.stVal U_A_AB_DEAD Low phsA or phsAB voltage 1=Low voltage
1 216 .VDeaPhsB.stVal U_B_BC_DEAD Low phsB or phsBC voltage 1=Low voltage
1 217 .VDeaPhsC.stVal U_C_CA_DEAD Low phsC or phsCA voltage 1=Low voltage
2.3.65 LD0.CMMXU1 Phase current limit supervision (1)
Table 67: LD0.CMMXU1 Phase current limit supervision (1)
Object type
Addr IEC 61850 name SA name Description Values
LD0.CMMXU1
1 4701 .HiAlm.stVal HIGH_ALARM High alarm 1=Alarm
1 4702 .HiWrn.stVal HIGH_WARN High warning 1=Warning
1 4703 .LoWrn.stVal LOW_WARN Low warning 1=Warning
1 4704 .LoAlm.stVal LOW_ALARM Low alarm 1=Alarm
2.3.66 LD0.RESCMMXU1 Residual current limit supervision (1)
Table 68: LD0.RESCMMXU1 Residual current limit supervision (1)
Object type
Addr IEC 61850 name SA name Description Values
LD0.RESCMMXU1
1 4709 .HiAlm.stVal HIGH_ALARM High alarm 1=Alarm
1 4710 .HiWrn.stVal HIGH_WARN High warning 1=Warning