2.3.56 CTRL.ESSXSWI2 Earthing switch indication (2)
Table 58: CTRL.ESSXSWI2 Earthing switch indication (2)
Object type Addr IEC 61850 name SA name Description Values
CTRL.ESSXSWI2
2 7080 .Pos.stVal POSITION Interm.=0; Off=1; On=2; Bad=3 0...3
2.3.57 LD0.DARREC1 Autorecloser (1)
Table 59: LD0.DARREC1 Autorecloser (1)
Object type Addr IEC 61850 name SA name Description Values
LD0.DARREC1
1 2806 SucRec.stVal Succesful reclose 1=Success
1 2819 .ArOn.stVal - AR on/off 1=On
1 2801 .PrgRec1.stVal INPRO_1 AR 1st reclose 1=In progress
1 2802 .PrgRec2.stVal INPRO_2 AR 2nd reclose 1=In progress
1 2803 .PrgRec3.stVal INPRO_3 AR 3rd reclose 1=In progress
1 2804 .PrgRec4.stVal INPRO_4 AR 4th reclose 1=In progress
1 2805 .PrgRec5.stVal INPRO_5 AR 5th reclose 1=In progress
1 2800 .PrgRec.stVal INPRO AR in progress 1=In progress
1 2814 .CBManCls.stVal MAN_CB_CL CB manually closed 1=CB closed
1 2808 .LO.stVal LOCKED Lockout status 1=Lockout
1 2807 .UnsRec.stVal UNSUC_RECL Reclose fail status 1=Failed
1 2809 .RdyRec.stVal READY Ready reclose status 1=Ready
1 2810 .ActRec.stVal ACTIVE Active reclose status 1=Active
1 2811 .PrgDsr.stVal DISCR_INPRO Discrimination time in p. 1=In progress
1 2812 .PrgCutOut.stVal CUTOUT_INPRO Cutout time in progress 1=In progress
1 2813 .FrqOpAlm.stVal FRQ_OP_ALM Frequent operation alarm 1=Alarm
1 2815 .Op.general CLOSE_CB Operate (close XCBR) 1=Close CB
1 2816 .OpOpn.general OPEN_CB Operate (open XCBR) 1=Open CB
1 2817 .UnsCBCls.stVal UNSUC_CB CB closing failed 1=Failed
1 2818 .WtMstr.stVal CMD_WAIT Master signal to follower 1=Signal
2.3.58 LD0.SECRSYN1 Synchrocheck (1)
Table 60: LD0.SECRSYN1 Synchrocheck (1)
Object type
Addr IEC 61850 name SA name Description Values
LD0.SECRSYN1
1 1136 .SynPrg SYNC_INPRO Synch. in progress 1=In progress
1 1134 .FailCmd CMD_FAIL_AL Close request fail 1=Failed
1 1135 .FailSyn CL_FAIL_AL Close cmd fail 1=Failed