2.3.38 LD0.T1PTTR1 Thermal overload protection (1)
Table 40: LD0.T1PTTR1 Thermal overload protection (1)
Object type Addr IEC 61850 name SA name Description Values
LD0.T1PTTR1
1 1200 .Str.general START General start 1=Start
1 1198 .AlmThm.general ALARM Thermal alarm 1=Alarm
1 1199 .Op.general OPERATE General operate 1=Operate
2.3.39 CTRL.Cxxxxx1 Circuit breaker - CB object and failure
protection (1)
Table 41: CTRL.Cxxxxx1 Circuit breaker - CB object and failure protection (1)
Object type Addr IEC 61850 name SA name Description Values
CTRL.CBCILO1
1 3000 .EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
1 3001 .EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
1 3002 .ItlByPss.stVal ITL_BYPASS Interlocking bypass 1=Bypassed
CTRL.CBCSWI1
2 7001 .Pos.stVal POSITION Interm.=0; Off=1; On=2; Bad=3 0...3
1 3003 .Pos.stSeld SELECTED CB selected 1=Selected
CTRL.CBCXCBR1
1 3004 .BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
1 3005 .BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
CTRL.CCBRBRF1
1 3008 .OpEx.general TRBU Failure ext.trip 1=Failure
1 3009 .OpIn.general TRRET Operate, re-trip 1=Operate
1 3010 .Str.general CB_FAULT_AL Start, timer running 1=Start
2.3.40 LD0.INRPHAR1 Three-phase inrush detection (1)
Table 42: LD0.INRPHAR1 Three-phase inrush detection (1)
Object type
Addr IEC 61850 name SA name Description Values
LD0.INRPHAR1
1 903 .Str.general START General start 1=Start
1 904 .Str.phsA phase A start 1=Start
1 905 .Str.phsB phase B start 1=Start
1 906 .Str.phsC phase C start 1=Start
1MRS757824 C Section 2
IEC 60850-5-101/104 data mappings
Recloser Protection and Control RER615 27
Point List Manual