2.6.2 General device data
Table 103: General device data
Object type Addr IEC 61850 name SA name Description Values
LD0.LLN0
50 20000 .LEDRs1.ctlVal LED reset 1 1=Reset
50 20001 .LEDRs2.ctlVal LED reset 2 1=Reset
LD0.LHDP1
50 20013 .RsDev.ctlVal Reset device 1=Reset
LD0.LLN0
50 41001 .ActSG1.ctlVal Activate setting group 1 1=Activate
50 41002 .ActSG2.ctlVal Activate setting group 2 1=Activate
50 41003 .ActSG3.ctlVal Activate setting group 3 1=Activate
50 41004 .ActSG4.ctlVal Activate setting group 4 1=Activate
50 41005 .ActSG5.ctlVal Activate setting group 5 1=Activate
50 41006 .ActSG6.ctlVal Activate setting group 6 1=Activate
2.6.3 CTRL.Cxxxxx1 Circuit breaker control (1)
Table 104: CTRL.Cxxxxx1 Circuit breaker control (1)
Object type
Addr IEC 61850 name SA name Description Values
CTRL.CBCSWI1
51 21000 .Pos.Oper.ctlVal - Circuit breaker control 2/1=On/Off
2.6.4 LD0.DARREC1 Autoreclosing reset signals (1)
Table 105: LD0.DARREC1 Autoreclosing reset signals (1)
Object type
Addr IEC 61850 name SA name Description Values
LD0.DARREC1
50 20003 .ResCnt.Oper.ctlVal - AR reset all counters 1=Reset
50 20004 .RsRec.Oper.ctlVal - AR reset 1=Reset
1MRS757824 C Section 2
IEC 60850-5-101/104 data mappings
Recloser Protection and Control RER615 47
Point List Manual