2.3.35 LD0.NSPTOV1 Negative-sequence overvoltage protection
(1)
Table 37: LD0.NSPTOV1 Negative-sequence overvoltage protection (1)
Object type Addr IEC 61850 name SA name Description Values
LD0.NSPTOV1
1 966 .Str.general START General start 1=Start
1 965 .Op.general OPERATE General operate 1=Operate
2.3.36 LD0.FRPFRQ1 Frequency protection (1)
Table 38: LD0.FRPFRQ1 Frequency protection (1)
Object type Addr IEC 61850 name SA name Description Values
LD0.FRPTRC1
1 889 .Str.general START Stage 1 start 1=Start
1 LD0.FRPTOF1 Overfrequency
1 883 .Op.general OPR_OFRQ operate 1=Operate
1 LD0.FRPTUF1 Underfrequency
1 895 .Op.general OPR_UFRQ operate 1=Operate
1 LD0.FRPFRC2 Frequency gradient
1 877 .Op.general OPR_FRG operate 1=Operate
2.3.37 LD0.FRPFRQ2 Frequency protection (2)
Table 39: LD0.FRPFRQ2 Frequency protection (2)
Object type
Addr IEC 61850 name SA name Description Values
LD0.FRPTRC2
1 890 .Str.general START Stage 2 start 1=Start
1 LD0.FRPTOF2 Overfrequency
1 884 .Op.general OPR_OFRQ operate 1=Operate
1 LD0.FRPTUF2 Underfrequency
1 896 .Op.general OPR_UFRQ operate 1=Operate
1 LD0.FRPFRC2 Frequency gradient
1 878 .Op.general OPR_FRG operate 1=Operate