7.2.2 Link SYNCHROTACT - PC via network
Cable: 1:1 (not crossed)
Preparation of SYNCHROTACT 5: Get the address from the local network
administrator and set it in SYNCHROTACT 5 by means of SynView. For that, connect
the PC directly to the SYNCHROTACT (see section 7.2.1) and start SynView with the
existing IP address of the device.
Afte the setting has been carried out, the address must be activated by switching off and
on the auxiliary voltage.
Preparation of the PC: open SynView and set IP address of the desired device.
7.2.3 SynView Operating Instructions
SynView can be used with an optional password. That way the access rights are limited.
The standard password after installation of SynView is 1234. As long as this password is
not changed, the access is automatically unlimited (e.g. during commissioning). If the
password is changed all write commands are blocked in "logout-status" (red hand). The
"login" (green hand) takes place by entering the password and enables all functions.
A logout can be done manually or is automatically done 8 hours after the last write
command.