As shown in Table 5-5 the meaning of each abbreviated word is:
Transaction identier hi: Transaction Identier high byte
Transaction identier lo: Transaction Identier low byte
Protocol identier hi: Protocol Identier high byte
Protocol identier lo: Protocol Identier low byte
Length hi: length high byte
Length lo: length low byte
Unit identier: slave address
Fun: function code
Data start reg hi: start register address high byte
Data start reg lo: start register address low byte
Data #of regs hi: number of register high byte
Data #of regs lo: number of register low byte
a. Read Status Relay (Function Code 01)
Function Code 01
This function code is used to read relay status in Acuvim II series meter.
1=On 0=O
There are 8 Relays in the meter, and the starting address is 0000H.
The following query is to read 2 Relays Status of the meter Address 1.