4.6 Time of use (TOU)
User can assign up to 4 different tariffs (sharp, peak, valleyand normal) to
dierent time period within a day according to the billing requirements. The
meter will calculate and accumulate energy to dierent taris according to the
meters internal clock timing and TOU settings.
TOU setting: User can set a maximum of 12 TOU seasons, each season can be
assigned to a TOU schedule (a maximum of 14 TOU schedules are available).
Each schedule can be divided up into 14 segments (in which each segment can
have its own tari ).User can customize the TOU calendar (including its taris,
seasons, schedules and segments) according to dierent applications. To make
sure that the TOU calendar is setup correctly, the meter will check the TOU
settings according to the predened rules (see below for TOU setting format
requirement” for details).TOU function will be disabled if the TOU calendar is
set up incorrectly. If no errors are found in the calendar and the TOU function is
enabled, TOU energyaccumulation will begin.
TOU setting format requirement:
1. Season setting parameter: The calendar year will be divided up into dierent
seasons depending on the season setting parameter. The parameter can be
selected from any integer between 1 to 12. User must enter the correct value
for the season setting parameter in accordance to the TOU season table. If the
season setting parameter is set as 2, the first 2 slots of the TOU season table
must be set, otherwise it will be considered as an invalid input (TOU function
will be disabled).
2. TOU season format: Enter the start date into the TOU season table slot
following this format “MM-DD ID” - MM stands for the month, DD stands for the
day and ID stands for the TOU schedule ID (available from 01 to 14). The dates
should be organized so that they are in sequence according to the calendar

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AccuEnergy Acuvim II series and is the answer not in the manual?

AccuEnergy Acuvim II series Specifications

General IconGeneral
BrandAccuEnergy
ModelAcuvim II series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals