259
Address Parameter Code Relationship
Data
type
Property
3302EH~302FH
Phase B apparent
power Sb
F1 S=Rx×(PT1/PT2)×(CT1/CT2) oat R
3030H~3031H
Phase C apparent
power Sc
F1 S=Rx×(PT1/PT2)×(CT1/CT2) oat R
3032H~3033H
System apparent
power Ssum
F1 S=Rx×(PT1/PT2)×(CT1/CT2) oat R
3034H~3035H
Phase A power factor
PFa
F1 PF = Rx oat R
3036H~3037H
Phase B power factor
PFb
F1 PF = Rx oat R
3038H~3039H
Phase C power factor
PFc
F1 PF = Rx oat R
303AH~303BH
System power factor
PFsum
F1 PF = Rx oat R
6.3.7 Metering Parameter Address Table
Basic Analog measurements
There are two different modes to read basic analog measurements, one
is secondary mode, and another is primary mode. In primary mode, the
numerical value in the register of the meter is equal to the real physical value. In
secondary mode, the relationship between the numerical value in the register
and the real physical value is shown in the following table. (Rx is the numerical
value in register of Acuvim II series meter)
Function code: 03H for reading.