292
Table 6-53 data address of TOU
Address Parameter Range Data type
Type of
access
Basis parameter of TOU
7800H Season Number 0~12 Word R/W
7801H Schedule Number 0~14 Word R/W
7802H Segment Number 0~14 Word R/W
7803H Tari Number 0~3 Word R/W
7804H
Weekend Setting(bit0-Sunday;bit1~
bit6:Monday~Saturdaybit=1 means
using energy,bit=0 means not using
energy)
0~127 Word R/W
7805H Weekend Schedule 0~14 Word R/W
7806H Holiday Number 0~30 Word R/W
7807H Time of Use factory setting 1:enable Word R/W
7808H
Choice of calculation auto reset
(0: End of Momth)
1:enable Word R/W
7809H
TOU auto reset xed date:day
(default is 1)
Word R/W
780AH
TOU auto reset xed date:hour
(default is 0)
1~31 Word R/W
780BH
TOU auto reset xed date:minute
(default is 0)
0~23 Word R/W
Address Parameter Range
Data
type
Type of
access
7714H DST Ending First few weeks 1~5 Word R/W
7715H DST Ending Hour 0~23 Word R/W
7716H DST Ending Min 0~59 Word R/W
7717H DST Ending Adjust time (Unit: Min) 1~120 Default: 60 Word R/W
Data address of TOU parameter setting includes basis parameter of TOU, time
zone setting parameter of TOU, time table setting parameter of TOU and holiday
setting parameter of TOU. Function: 03 code, 10 reset.